Fences are very commonly found above retaining walls. If a fence is going to be added to the wall
during or after the wall’s construction several things need to be considered.
Impact structures or fence posts should be positioned a
minimum of 3 ft (0.9 m) from the back of top course to allow a properly
designed load for local overturning.
If fence posts must be placed within 3 ft (0.9 m) of the
back of the wall facing, the designer must consider the localized top of wall
overturning force into their design.
Common post footings are formed by using construction tubes
placed at desired on-center locations during construction. If posts are placed
after construction is complete, holes must be hand dug as using a power auger
will cause severe damage to the geogrid layers.
If the post design calls for an engineered product to solve
localized overturning forces, a product such as the Sleeve-IT System
can be specified. Sleeve-IT is a Stratagrid product designed for use in
segmental retaining walls to resist top of wall overturning forces from fences
and railing. (ref. BP, Chapter 12.2)
Allan Block is working to achieve our industry initiative of Zero Wall Failures. With our Best Practices Manual and experience in the industry we are trying to expand the knowledge base for the design of segmental retaining walls (SRW's) by communicating and educating the professionals in the industry. To see the full Best Practices Manual, visit allanblock.com to download today and keep an eye out for more industry Best Practice recommendations here.